Модуль аналогового входу VIPA SM331 331-1KF01
Order no. 331-1KF01
Type SM 331
General information
Note -
Features 8 inputs 13 bit
Voltage, current
Resistance
Resistance thermometer
SPEED-Bus -
Current consumption/power loss
Current consumption from backplane bus 255 mA
Power loss 1.3 W
Technical data analog inputs
Number of inputs 8
Cable length, shielded 50 m
Rated load voltage -
Current consumption from load voltage L+ (without load) -
Voltage inputs
Min. input resistance (voltage range) 100 kOhm
Input voltage ranges -50 mV ... +50 mV
-500 mV ... +500 mV
-1 V ... +1 V
-5 V ... +5 V
0 V ... +10 V
-10 V ... +10 V
+1 V ... +5 V
Operational limit of voltage ranges +/-0.5% ... +/-0.6%
Operational limit of voltage ranges with SFU -
Basic error limit voltage ranges +/-0.3% ... +/-0.4%
Basic error limit voltage ranges with SFU -
Destruction limit current -
Current inputs
Max. input resistance (current range) 100 Ohm
Input current ranges -20 mA ... +20 mA
0 mA ... +20 mA
+4 mA ... +20 mA
Operational limit of current ranges +/-0.5%
Operational limit of current ranges with SFU -
Radical error limit current ranges with SFU +/-0.3%
Radical error limit current ranges with SFU -
Destruction limit current inputs (electrical current) -
Destruction limit current inputs (voltage) -
Resistance inputs
Resistance ranges 0 ... 600 Ohm
0 ... 6000 Ohm
www.vipa.com
© by VIPA GmbH, Ohmstr. 4, 91074 Herzogenaurach, Germany
All data with reservation and subject to change.
Publish date: 13.05.2015
Page 2/3
Operational limit of resistor ranges +/-0.5%
Operational limit of resistor ranges with SFU -
Basic error limit +/-0.3%
Basic error limit with SFU -
Destruction limit resistance inputs -
Resistance thermometer inputs
Resistance thermometer ranges Pt100
Ni100
Ni1000
Operational limit of resistance thermometer ranges +/-1K ... +/-1.2K
Operational limit of resistance thermometer ranges with SFU -
Basic error limit thermoresistor ranges +/-0.8K
Basic error limit thermoresistor ranges with SFU -
Destruction limit resistance thermometer inputs -
Thermocouple inputs -
Thermocouple ranges -
Operational limit of thermocouple ranges -
Operational limit of thermocouple ranges with SFU -
Basic error limit thermoelement ranges -
Basic error limit thermoelement ranges with SFU -
Destruction limit thermocouple inputs -
Programmable temperature compensation -
External temperature compensation -
Internal temperature compensation -
Internal temperature compensation -
Technical unit of temperature measurement -
Resolution in bit 13
Measurement principle Sigma-Delta
Basic conversion time 61 ms/51 ms / channel
Noise suppression for frequency 50 Hz/60 Hz
Initial data size 16 Byte
Status information, alarms, diagnostics
Status display none
Interrupts no
Process alarm no
Diagnostic interrupt no
Diagnostic functions no
Diagnostics information read-out none
Supply voltage display none
Group error display none
Channel error display none
Isolation
Between channels -
Between channels of groups to -
Between channels and backplane bus
Between channels and power supply -
Max. potential difference between circuits -
Max. potential difference between inputs (Ucm) DC 2 V
www.vipa.com
© by VIPA GmbH, Ohmstr. 4, 91074 Herzogenaurach, Germany
All data with reservation and subject to change.
Publish date: 13.05.2015
Page 3/3
Max. potential difference between Mana and Mintern (Uiso) -
Max. potential difference between inputs and Mana (Ucm) -
Max. potential difference between inputs and Mintern (Uiso) DC 75 V/ AC 60 V
Max. potential difference between Mintern and outputs -
Insulation tested with DC 500 V
Datasizes
Input bytes 16
Output bytes 0
Parameter bytes 21
Diagnostic bytes 0