Data sheet 6ES7131-0BL10-0XB0
*** SPARE PART*** SIMATIC DP, ELECTRONIC MODULE
DIGITAL, FOR ET 200B, W=235MM, 32DI 24V DC, 0.2MS INPUT
DELAY
Supply voltage
Rated value (DC) 24 V; L5+; value at t < 0.5 s: 35 V
permissible range, lower limit (DC) 18.5 V
permissible range, upper limit (DC) 30.2 V
Input current
Current consumption, typ. 70 mA; From L5+; logic
Current consumption, max. 1 000 mA; from L5+; sensor
I²t 0.05 A²·s; with starting current inrush
Power loss
Power loss, typ. 4.8 W
Hardware configuration
Rack
● required terminal block TB2/DC, TB2-4/DC, TB4/DC, TB4-4/DC
Digital inputs
Number of digital inputs 32
Input voltage
● Rated value (DC) 24 V
● for signal “0” -30 to +5V
● for signal “1” 13 to 30V
Input current
● for signal “1”, typ. 4 mA; At 24 V min. 2 mA
Input delay (for rated value of input voltage)
for standard inputs
— at “0” to “1”, max. 0.2 ms
Cable length
● unshielded, max. 100 m
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire
sensor), max.
1.5 mA
Interfaces
PROFIBUS DP
6ES7131-0BL10-0XB0 Changes preserved
Page 1/
3
16.06.2016 © Copyright Siemens AG
● Transmission rate, max. 12 Mbit/s
● FREEZE capability Yes
Protocols
Bus protocol/transmission protocol PROFIBUS DP
Interrupts/diagnostics/status information
Diagnostics indication LED
● RUN LED Yes
● Bus fault BF (red) Yes
● Status indicator digital input (green) Yes
Potential separation
between electronic block and PROFIBUS DP Yes
Potential separation digital inputs
● Potential separation digital inputs No
Degree and class of protection
Degree of protection acc. to EN 60529 IP20
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. 0 °C
● horizontal installation, max. 60 °C; 40°C for other mountings
Air pressure acc. to IEC 60068-2-13
● permissible range, lower limit 795 hPa
● permissible range, upper limit 1 080 hPa
Relative humidity
● Operation, min. 95 %
● Operation, max. 15 %; RH class 2 in accordance with IEC 1131-2
Vibrations
● Operation, tested according to IEC 60068-2-6 Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075
mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock test
● tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Connection method
Inputs/outputs Screw-type and spring-loaded terminals, permanent wiring; 3 and
4-wire connection
Dimensions
Width 235 mm; EB and TB
Height 130 mm; EB and TB
Depth 60 mm; EB and TB
Weights
Weight, approx. 800 g; EB and TB