Перетворювач частоти Schneider Altivar ATV21WU55N4C 5.5 кВт

Відкласти Порівняти
0
Артикул: 2215
Schneider
Характеристики

Стан   —   Новий

21106 грн./шт:
У наявності
Range of productAltivar 21
Product or component typeVariable speed drive
Product destinationAsynchronous motors
Product specific applicationPumps and fans in HVAC
Assembly styleWith heat sink
Component nameATV21
EMC filterClass B EMC filter integrated
power supply voltage380...480 V - 15...10 %
Network number of phases3 phases
Motor power kW5.5 kW
Motor power hp7.5 hp
Line current11 A at 380 V
8.7 A at 480 V
Speed range1…10
Transient overtorque120 % of nominal motor torque +/- 10 % for 60 s
Asynchronous motor control profileQuadratic voltage/frequency ratio
Constant voltage/frequency ratio
Current flux vector control (FVC) without speed feedback
Energy saving ratio
Constant voltage/frequency ratio with automatic IR compensation
Communication port protocolModbus
type of polarizationNo impedance
IP degree of protectionIP54 conforming to EN 60530
IP54 conforming to EN 61800-5-2
IP54 conforming to IEC 60529
IP54 conforming to IEC 61800-5-1
Option cardCommunication card for APOGEE FLN
Communication card for BACnet
Communication card for LonWorks
Communication card for METASYS N2
Complementary
power supply voltage limits323…528 V
power supply frequency50...60 Hz - 5...5 %
power supply frequency limits47.5…63 Hz
Apparent power9.1 kVA at 380 V
maximum prospective line Isc22 kA
maximum continuous output current12 A at 380 V
12 A at 460 V
Maximum transient current13.2 A for 60 s
Speed drive output frequency0.5…200 Hz
Nominal switching frequency12 kHz
Switching frequency12...16 kHz with derating factor
6...16 kHz adjustable
Speed accuracy+/- 10 % of nominal slip for 0.2 Tn to Tn torque variation
Torque accuracy+/- 15 %
Regulation loopAdjustable PI regulator
Motor slip compensationAutomatic whatever the load
Not available in voltage/frequency ratio motor control
Adjustable
diagnostic1 LED (red) for DC bus energized
Output voltage<= power supply voltage
InsulationElectrical between power and control
recommended type of cable for mounting in an enclosureWith UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Electrical connectionL1/R, L2/S, L3/T: terminal 6 mm² / AWG 10
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14
Tightening torque1.3 N.m, 11.5 lb.in (L1/R, L2/S, L3/T)
0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
SupplyInternal supply: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
Analogue input number2
Analogue input typeVIA switch-configurable current: 0...20 mA, impedance: 242 Ohm, resolution 11 bits
VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 11 bits
VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm
VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 11 bits
Sampling durationF 2 ms +/- 0.5 ms for discrete input(s)
R 2 ms +/- 0.5 ms for discrete input(s)
RES 2 ms +/- 0.5 ms for discrete input(s)
VIA 2 ms +/- 0.5 ms for analog input(s)
VIB 2 ms +/- 0.5 ms for analog input(s)
Response timeFLA, FLC 7 ms +/- 0.5 ms for discrete output(s)
FLB, FLC 7 ms +/- 0.5 ms for discrete output(s)
FM 2 ms +/- 0.5 ms for analog output(s)
RY, RC 7 ms +/- 0.5 ms for discrete output(s)
Accuracy+/- 1 % (FM) for a temperature variation 60 °C
+/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C
Linearity errorFM: +/- 0.2 % for output
VIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input
Analogue output number1
Analogue output typeFM switch-configurable current 0...20 mA, impedance: 500 Ohm, resolution 10 bits
FM switch-configurable voltage 0...10 V DC, impedance: 470 Ohm, resolution 10 bits
Discrete output number2
Discrete output typeConfigurable relay logic: (FLA, FLC) NO - 100000 cycles
Configurable relay logic: (FLB, FLC) NC - 100000 cycles
Configurable relay logic: (RY, RC) NO - 100000 cycles
Minimum switching current3 mA at 24 V DC for configurable relay logic
Maximum switching current2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
Discrete input typeF programmable 24 V DC, with level 1 PLC, impedance: 3500 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 3500 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 3500 Ohm
Discrete input logicNegative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)
Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Acceleration and deceleration rampsLinear adjustable separately from 0.01 to 3200 s
Automatic based on the load
Braking to standstillBy DC injection
Protection typeAgainst input phase loss: drive
Break on the control circuit: drive
Input phase breaks: drive
Line supply overvoltage and undervoltage: drive
Line supply undervoltage: drive
Overcurrent between output phases and earth: drive
Overheating protection: drive
Overvoltages on the DC bus: drive
Short-circuit between motor phases: drive
Thermal power stage: drive
Motor phase break: motor
Thermal protection: motor
With PTC probes: motor
Against exceeding limit speed: drive
Insulation resistance>= 1 mOhm 500 V DC for 1 minute
Frequency resolutionAnalog input: 0.024/50 Hz
Display unit: 0.1 Hz
Connector type1 RJ45
Physical interface2-wire RS 485
Transmission frameRTU
Transmission rate9600 bps or 19200 bps
Data format8 bits, 1 stop, odd even or no configurable parity
Number of addresses1…247
Communication serviceWrite single register (06)
Write multiple registers (16) 2 words maximum
Time out setting from 0.1 to 100 s
Read device identification (43)
Monitoring inhibitable
Read holding registers (03) 2 words maximum

Швидке замовлення